Free generator maintenance checklist

Free generator maintenance checklist (PDF-ready). Covers diesel and portable generators: fuel, oil, coolant, electrical and load testing. Download free.

Updated 2 May 2026

Generator Maintenance Checklist

Inspection, servicing and load test log | Diesel Petrol Standby generators

Live form
0 of 39 checks

A - Visual Inspection

1External condition: no significant damage, corrosion or contamination
2Fuel tank: no leaks, cap present and sealed, level adequate
3Fuel lines and connections: no leaks, no damage or chafing
4Exhaust system: no leaks, guards in place, no blockage
5Air intake and air filter: no blockage, filter condition acceptable
6Cooling system - radiator: fins clean, no damage
7Cooling system - hoses: no cracks, secure, no leaks
8Cooling system - coolant level: within range
9Cooling system - fan: blades intact, guards in place
10Battery: terminals clean and secure, no corrosion
11Battery cables: no damage, secure connections
12Control panel: no damage, moisture or loose connections

B - Fluid Checks

13Engine oil level: within range (record level if possible)
14Engine oil condition: colour and viscosity acceptable, no contamination
15Engine oil - visible leaks: none
16Coolant level: within range
17Coolant concentration: tested, within specification
18Coolant - visible leaks: none
19Fuel level: adequate
20Fuel quality: no water or sediment contamination
21Fuel filter / water separator: condition acceptable, not due for replacement

C - Electrical Checks

22Battery voltage: within specification (record V)
23Battery charger: operational
24Transfer switch (if fitted): operational, correct mode
25Circuit breakers: no tripped breakers, condition acceptable
26Output connections and cables: secure, no damage
27Earth / ground connection: secure and correct
28Emergency stop button: tested and functional
29Control panel indicators and alarms: functional

D - Operational Test (Run Under Load)

30Starts within normal cranking attempts
31Idle and full-load RPM: correct
32Oil pressure: within specification (record kPa if available)
33Coolant temperature: within specification
34Voltage output: stable at rated voltage (record V)
35Frequency output: stable at 50 Hz (record Hz)
36No abnormal noises or vibrations
37Exhaust smoke: colour acceptable (no heavy black or white smoke)
38Auto-start function (if fitted): tested and functional
39Load transfer (if transfer switch fitted): smooth, no interruption

How to use: download the PDF, print or complete digitally on any device.

  • PDF format, ready to print or fill on screen
  • Use as-is or customise to suit your operation
  • Go digital in MapTrack for photos, alerts and audit trails

Download free PDF template

Use in MapTrack →
FreePDFUpdated May 2026

Get your free template

Enter your email to download the generator maintenance checklist as a free PDF. No sign-up required to use it.

Rated 4.9 on G2Rated 5.0 on Capterra
Your info is secure. No spam, ever.

These templates are free general guides provided as-is. They do not constitute legal, safety or compliance advice. You are responsible for ensuring any form meets your specific workplace obligations, industry standards and applicable regulations.

G2 rating 4.9 out of 5Capterra rating 5.0 out of 5

Trusted by teams across Australia and New Zealand

We respect your privacy. Unsubscribe anytime.

Or set it up in MapTrack

  • Fill it in on a phone, attach photos to any check
  • Automatic reports and audit trails
  • The same checks as the PDF, ready to configure

Free 30-day trial. No credit card. Personal email accepted.

Don't just download it - use it live. Start a free workspace with this generator maintenance checklist already built, so your crew can run it from a phone.

Jarrod Milford

Jarrod Milford

Commercial Director

Updated 2 May 2026

Key takeaways

  • The MapTrack generator maintenance checklist contains 39 checks across 4 sections. Sections covered: A - Visual Inspection, B - Fluid Checks, C - Electrical Checks, D - Operational Test (Run Under Load).

Enter your email below to download this generator maintenance checklist as a ready-to-use PDF.

Used by construction, mining and field service teams

Saunders InternationalMineral ResourcesSupagasHacer GroupMetro TunnelUltrabuilt

What is a generator maintenance checklist?

A generator maintenance checklist is a structured inspection and service form used to verify a generator's mechanical, electrical and safety condition. Unlike a simple pre-start check, a maintenance checklist covers both current condition and upcoming preventive maintenance tasks such as oil changes, filter replacements and load testing. Regular maintenance is critical for generators because they are often relied upon in emergencies or for continuous power on remote sites. A failed generator due to missed maintenance can halt an entire operation. The checklist supports AS/NZS 3010 compliance for electrical installations and generator-specific manufacturer service requirements.

Generators are classified as electrical plant under Australian WHS legislation, and their maintenance is governed by multiple regulatory frameworks. AS/NZS 3010:2017, Section 7 covers maintenance and testing requirements for generating sets, including load testing, earthing verification and protective device testing. For transportable generators commonly used on construction sites, AS 2790:2020 sets additional requirements for fuel systems, exhaust guarding and RCD protection. Skipping scheduled generator maintenance creates a cascade of risks: fuel contamination from water ingress leads to injector damage, unmaintained coolant degrades and causes overheating, and corroded battery terminals prevent starting precisely when backup power is needed most. On remote mine sites and hospital facilities where generators provide essential or life-safety power, a maintenance failure can have consequences ranging from production losses to patient safety incidents.

Learn more about maintenance and work orders in MapTrack.

Benefits of using this generator maintenance checklist

  • Reliable power when it matters most: regular maintenance prevents failures during critical operations or emergencies.
  • Extended generator life: oil, coolant and filter changes at the correct intervals protect the engine.
  • AS/NZS 3010 compliance: documented inspections support electrical installation compliance requirements.
  • Early fault detection: identifying fuel contamination, coolant leaks or battery issues before they cause failure.
  • Cost savings: preventive maintenance is substantially cheaper than emergency repair or generator replacement.
  • Maintenance history per asset: a signed maintenance record for every inspection supports audits and warranty claims.

Benefits of digitising forms in MapTrack

When you digitise generator checklists in MapTrack, you get:

  • Field users can easily scan a QR code to complete a form on mobile. Unlimited users.
  • Automatically get alerts when faults are identified.
  • Link every form digitally as a PDF to the relevant asset, location or person.
  • Receive a digital PDF copy with every submission to your email.
  • Ability to share forms digitally.
  • Build conditional logic (show or hide questions based on answers).
  • Take pictures or attach photos. Not possible with a paper-based form.
  • Electronic signatures.
  • Edit forms later without reprinting.
  • Restrict permissions (who can view, complete or approve).
  • Build forms with AI (describe what you need and MapTrack suggests the form).
  • Trigger work orders automatically when a fault is logged during an inspection.
  • Track service intervals by hours, kilometres or calendar date in one place.
  • Attach supplier invoices and parts receipts to each maintenance record.

Book a demo to see how MapTrack handles generator checklists.

Try MapTrack free for 30 days

Full access to every feature. No credit card required. Per-asset pricing so you scale as your fleet grows.

  • No credit card required
  • 30 days free trial
  • Cancel anytime

1-2 days/week saved

Bloody amazing! We used to spend 1-2 days a week tracking and managing our generators alone.
Saunders International

Steve McAllister

Asset Coordinator, Saunders International

What to include in a generator maintenance checklist

This generator maintenance checklist covers 7 key areas:

  • Generator details: generator ID, make/model, rated output (kVA/kW), fuel type, site/location, date, technician name, hour meter, last service date and hours.
  • Visual inspection: external condition, fuel tank and lines (leaks, cap seal), exhaust system, air intake and filter, cooling system (radiator, hoses, fan, coolant level), battery and cables, control panel.
  • Fluid checks: engine oil (level, condition, leaks), coolant (level, concentration, leaks), fuel level and quality (water/sediment), fuel filter/water separator condition.
  • Electrical checks: battery voltage, charger operational, transfer switch (if fitted), circuit breakers, output connections, earth/ground connection, emergency stop.
  • Operational test (under load): starts within normal cranking time, oil pressure, coolant temperature, voltage and frequency output stable, no abnormal noise or vibration, exhaust smoke colour, auto-start function (if fitted).
  • Preventive maintenance due dates: next oil change, next fuel filter change, next air filter change, next coolant change, next load bank test.
  • Defects and sign-off: defect description, reported to, generator fit for use, technician signature and date.

How to use this generator maintenance checklist

  1. Fill in generator details at the top of the form including the current hour meter reading and last service date.: Record the generator ID, make, model, rated output (kVA/kW), fuel type, site location and controller type. Include the current hour meter reading and the date and hours of the last service to confirm the maintenance interval.
  2. Complete the visual inspection with the generator at rest: check external condition, fuel system, exhaust, air intake, cooling system, battery and control panel.: Walk around the generator checking for external damage, fuel leaks at the tank, lines and fittings, exhaust rust or damage, air intake blockage, coolant leaks at hoses and the radiator, battery terminal corrosion and control panel warning indicators. Record findings for each system area.
  3. Check all fluid levels. Assess fuel quality for water or sediment contamination. Run the electrical checks including battery voltage, earth connection and emergency stop.: Check engine oil on the dipstick, coolant at the overflow tank and fuel level on the gauge. Draw a small fuel sample from the tank drain to check for water or sediment. Measure battery voltage with a multimeter, which should read 12.4V or above. Verify the earth connection is secure. Test the emergency stop from all accessible locations.
  4. Run the generator under load and record output readings. Update the preventive maintenance due-dates section. Sign and date when complete.: Start the generator and connect to the building load or a load bank. Record voltage, frequency and temperature at rated load. Update the preventive maintenance section with the next due dates for oil change, fuel filter, air filter, coolant change and load bank test. Sign and date the completed form.

In MapTrack, you can schedule and track maintenance digitally. Each submission is stored as a timestamped PDF against the asset record.

Get the free templateEnter your email above to download the full generator maintenance checklist as a PDF.Back to download form

How often should you complete this checklist?

Generator maintenance frequency should follow the manufacturer's manual and your site requirements. As a general guide: weekly visual inspections and oil level checks for active standby generators; monthly load testing for standby units to verify operational readiness; oil and filter changes every 200–500 running hours or annually (whichever comes first); coolant changes every 2 years or as specified; and load bank testing at least annually in accordance with AS/NZS 3010. Site generators running continuously require more frequent service intervals. Track hours and calendar dates in your maintenance system to ensure nothing is missed.

Frequently asked questions

A generator maintenance checklist should cover visual inspection (external condition, fuel tank and lines, exhaust, air intake, cooling system, battery, control panel), fluid checks (engine oil level and condition, coolant level and concentration, fuel level and quality, fuel filter/water separator), electrical checks (battery voltage, charger, transfer switch, circuit breakers, earth/ground connection, emergency stop), and an operational test under load (oil pressure, coolant temperature, voltage and frequency output, auto-start function). Include a preventive maintenance due-dates section for oil, fuel filter, air filter and coolant changes.

Generator maintenance frequency depends on use and type. As a general guide: weekly visual inspections and oil level checks for standby generators; monthly load testing for standby units; and service intervals based on running hours (typically every 200 to 500 hours for oil and filter changes, or annually, whichever comes first). Consult the manufacturer\u2019s manual for your specific generator model. Site generators running continuously may require more frequent service. A maintenance schedule tied to hours and calendar intervals in your CMMS ensures nothing is missed.

A load test involves running a generator under a representative load, typically 75 to 100% of rated output, to verify it can handle the electrical demand placed on it in an emergency or operational scenario. Load testing confirms voltage stability, frequency, temperature control, and that protective devices work under real conditions. For standby generators, regular load testing (usually quarterly or annually) is required by AS/NZS 3010 and many insurance policies. Without periodic load testing, a generator may start but fail to carry load when it is actually needed.

Generator maintenance in Australia is governed by several standards. AS/NZS 3010:2017 (Generating Sets) covers installation, maintenance and testing requirements including load testing and earthing verification. AS 2790:2020 applies to transportable generating sets and addresses fuel systems, exhaust guarding and RCD protection. The WHS Regulations 2011, Chapter 5, require that plant including generators is maintained so it remains without risks to health and safety. AS/NZS 3000:2018 (Wiring Rules), Section 7.2, covers generating sets connected to installation wiring. Check your state or territory regulator for additional obligations.

Yes. Download and use the generator maintenance checklist for free. Open the file in your browser and use Print then Save as PDF. No MapTrack account is required. If you want to automate generator maintenance scheduling, track service history and running hours per asset, and receive alerts when service intervals are due, MapTrack can do that. Book a demo to see how.

Applicable regulatory standards

This template aligns with the following regulations and standards:

  • AS/NZS 3010:2017 - Generating Sets, Section 7: Maintenance and Testing
  • AS 2790:2020 - Electricity Generating Sets: Transportable (fuel systems, exhaust guarding, RCD protection)
  • WHS Regulations 2011, Chapter 5, Part 5.1 - Management of Risks of Plant in the Workplace
  • AS/NZS 3000:2018 - Wiring Rules, Section 7.2: Generating Sets Connected to Installation Wiring

The numbers behind this generator maintenance checklist

Every figure below is sourced and dated, so you can quote it in a toolbox talk, a budget case or a board paper without having to chase the original report.

Embed this free template on your website

Run an industry blog, trade association site, or training resource? Drop a preview of this free generator maintenance checklist straight into your page. The snippet is self-contained, needs no scripts, and links readers back to the full free template.

<div style="max-width:480px;font-family:system-ui,-apple-system,'Segoe UI',Roboto,sans-serif;border:1px solid #E5E7EB;border-radius:12px;padding:20px;background:#ffffff;">
  <p style="font-size:12px;font-weight:700;letter-spacing:0.05em;text-transform:uppercase;color:#071D49;margin:0;">Free template</p>
  <p style="font-size:18px;font-weight:700;color:#071D49;margin:6px 0 0;">Generator maintenance checklist</p>
  <ul style="margin:12px 0 0;padding-left:18px;color:#374151;font-size:14px;line-height:1.6;">
    <li style="margin:4px 0;">Generator details: generator ID, make/model, rated output (kVA/kW), fuel type, site/location, date, technician name, hour meter, last service date and hours.</li>
    <li style="margin:4px 0;">Visual inspection: external condition, fuel tank and lines (leaks, cap seal), exhaust system, air intake and filter, cooling system (radiator, hoses, fan, coolant level), battery and cables, control panel.</li>
    <li style="margin:4px 0;">Fluid checks: engine oil (level, condition, leaks), coolant (level, concentration, leaks), fuel level and quality (water/sediment), fuel filter/water separator condition.</li>
    <li style="margin:4px 0;">Electrical checks: battery voltage, charger operational, transfer switch (if fitted), circuit breakers, output connections, earth/ground connection, emergency stop.</li>
    <li style="margin:4px 0;">Operational test (under load): starts within normal cranking time, oil pressure, coolant temperature, voltage and frequency output stable, no abnormal noise or vibration, exhaust smoke colour, auto-start function (if fitted).</li>
    <li style="margin:4px 0;">Preventive maintenance due dates: next oil change, next fuel filter change, next air filter change, next coolant change, next load bank test.</li>
  </ul>
  <p style="font-size:13px;color:#6B7280;margin:14px 0 0;padding-top:12px;border-top:1px solid #E5E7EB;">Free <a href="https://www.maptrack.com/templates/generator-maintenance-checklist" style="color:#071D49;font-weight:600;text-decoration:none;">Generator maintenance checklist</a> by MapTrack</p>
</div>

Free to reuse, including commercially. This template is published under a Creative Commons Attribution 4.0 licence. Copy it, adapt it, put it on your own site or in your own docs. All we ask is that you credit MapTrack with a link back to this page. The snippet above already includes that credit, so if you use it as-is you’re covered.

Cite this template

Writing about this topic? You’re welcome to quote this checklist. Here’s the wording to use so your readers can find the original.

The MapTrack generator maintenance checklist contains 39 checks across 4 sections.

Short attribution
MapTrack Generator maintenance checklist, https://www.maptrack.com/templates/generator-maintenance-checklist
Reference list
MapTrack. (2026). Generator maintenance checklist [Checklist template]. Retrieved from https://www.maptrack.com/templates/generator-maintenance-checklist

Free to reuse with credit under a Creative Commons Attribution 4.0 licence. If you’d rather link straight to it, the page is https://www.maptrack.com/templates/generator-maintenance-checklist.

Need to schedule and track maintenance digitally?

Register every generator in MapTrack, attach digital forms, and get a complete history of every inspection, service and compliance record.

Maintenance and work orders · All templates · Pricing · Book a demo