Free PAT testing checklist

Free PAT testing checklist (PDF-ready). Visual inspection, earth continuity, insulation resistance and polarity per IET Code of Practice. Download free.

Updated 10 Aug 2026

PAT Testing Checklist

Portable appliance testing inspection and test record

Live form
0 of 30 checks

Pre-Test Checks

1Appliance class identified (Class I earthed, Class II double-insulated)
2Appliance unplugged and switched off before testing begins
3Test instrument in calibration, calibration date current

Visual Inspection

4Plug in good condition, no cracks, no exposed pins or damage
5Plug pins straight, secure, and free of corrosion or pitting
6Correct fuse rating fitted for appliance (moulded plugs noted)
7Flexible cord sheath intact, no cuts, abrasion or exposed conductors
8Cord free of joins, taping, kinks or repairs along its length
9Cord grip (anchorage) secure at plug and at appliance entry
10Appliance casing undamaged, no cracks or loose parts
11Guards, covers and access panels fitted and secure
12No signs of overheating, burn marks, or discolouration
13Ventilation openings clear of dust, lint and obstruction

Earth Continuity Test (Class I)

14Earth continuity reading within limit (less than 1 ohm including lead)
15Earth path confirmed between plug earth pin and exposed metal
16Reading stable when cord is flexed near plug and entry

Insulation Resistance Test

17Insulation resistance above minimum (Class I 1 M ohm, Class II 1 M ohm)
18No breakdown detected at 500 V DC test voltage
19Earth leakage / touch current within limit where alternative test used

Polarity Test (leads and cord sets)

20Active, neutral and earth correctly wired, no transposed conductors
21Extension lead and IEC cord set polarity confirmed end to end

Functional Check

22Appliance powers on and operates normally
23All switches and controls function correctly
24No unusual noise, smell, or vibration during operation
25RCD operates within trip time where appliance is RCD protected

Tagging & Records

26Durable tag fitted showing test date, next test due and tester ID
27Retest interval set per AS/NZS 3760 for the environment and equipment
28Appliance ID clearly marked and matches the asset register
29Result recorded in the test register / log
30Failed appliance removed from service, tagged out of service and reported

How to use: download the PDF, print or complete digitally on any device.

  • PDF format, ready to print or fill on screen
  • Use as-is or customise to suit your operation
  • Go digital in MapTrack for photos, alerts and audit trails

Download free PDF template

Use in MapTrack →
FreePDFUpdated Aug 2026

Get your free template

Enter your email to download the PAT testing checklist as a free PDF. No sign-up required to use it.

Rated 4.9 on G2Rated 5.0 on Capterra
Your info is secure. No spam, ever.

These templates are free general guides provided as-is. They do not constitute legal, safety or compliance advice. You are responsible for ensuring any form meets your specific workplace obligations, industry standards and applicable regulations.

G2 rating 4.9 out of 5Capterra rating 5.0 out of 5

Trusted by teams across Australia and New Zealand

We respect your privacy. Unsubscribe anytime.

Or set it up in MapTrack

  • Fill it in on a phone, attach photos to any check
  • Automatic reports and audit trails
  • The same checks as the PDF, ready to configure

Free 30-day trial. No credit card. Personal email accepted.

Don't just download it - use it live. Start a free workspace with this PAT testing checklist already built, so your crew can run it from a phone.

Jarrod Milford

Jarrod Milford

Commercial Director

Updated 10 August 2026

Key takeaways

  • The MapTrack PAT testing checklist contains 30 checks across 7 sections. Sections covered: Pre-Test Checks, Visual Inspection, Earth Continuity Test (Class I), Insulation Resistance Test, Polarity Test (leads and cord sets), Functional Check, Tagging & Records.

Enter your email below to download this PAT testing checklist as a ready-to-use PDF.

Used by construction, mining and field service teams

Saunders InternationalMineral ResourcesSupagasHacer GroupMetro TunnelUltrabuilt

What is a PAT testing checklist?

A PAT (Portable Appliance Testing) testing checklist is a structured document used to record the results of in-service inspection and testing of portable electrical equipment in the workplace. PAT testing is guided by the IET Code of Practice for In-Service Inspection and Testing of Electrical Equipment (5th Edition, 2020), which provides a framework for managing the safety of electrical equipment through a combination of visual inspection and electrical testing. The checklist covers the user check (daily visual), formal visual inspection (periodic, more detailed) and combined inspection and test (periodic, with electrical tests). Visual inspection items include the plug (condition, correct fuse rating, no damage to pins), cable (no cuts, kinks, joins, damage to outer sheath), equipment body (casing intact, no damage, ventilation clear, no signs of overheating or water ingress), and labelling (rated for the supply, correct voltage and frequency). Electrical tests include earth continuity (for Class I equipment, confirming the earth conductor provides a low-resistance path), insulation resistance (confirming adequate insulation between live conductors and accessible metal parts), polarity (where applicable, confirming live and neutral are correctly connected), and functional checks. Results are recorded alongside a pass or fail outcome, and each item is given a unique identification number and a test label showing the test date and next test due date.

Learn more about compliance and inspections in MapTrack.

Benefits of using this PAT testing checklist

  • Electrical safety: systematic testing identifies damaged plugs, frayed cables, faulty earth connections and insulation breakdown before they cause electric shock or fire.
  • Legal compliance: meet the Electricity at Work Regulations 1989 (UK) obligation to maintain electrical equipment in a safe condition. The IET Code of Practice provides the accepted methodology.
  • Risk-based approach: the IET Code of Practice allows organisations to set inspection and testing intervals based on the type of equipment, its use environment and the competence of users, avoiding unnecessary over-testing.
  • Insurance and audit support: a complete PAT testing register with test results, pass/fail outcomes and unique asset IDs provides documented evidence for insurers, landlords and health and safety audits.
  • Equipment accountability: each item receives a unique identification number and test label, supporting asset tracking and preventing untested equipment from entering service.
  • Cost control: identifying failing appliances early allows planned replacement rather than emergency action after an incident.

Benefits of digitising forms in MapTrack

When you digitise portable appliances checklists in MapTrack, you get:

  • Field users can easily scan a QR code to complete a form on mobile. Unlimited users.
  • Automatically get alerts when faults are identified.
  • Link every form digitally as a PDF to the relevant asset, location or person.
  • Receive a digital PDF copy with every submission to your email.
  • Ability to share forms digitally.
  • Build conditional logic (show or hide questions based on answers).
  • Take pictures or attach photos. Not possible with a paper-based form.
  • Electronic signatures.
  • Edit forms later without reprinting.
  • Restrict permissions (who can view, complete or approve).
  • Build forms with AI (describe what you need and MapTrack suggests the form).
  • Set recurring audit schedules with automatic reminders and escalation.
  • Produce regulator-ready PDF compliance packs in one click.
  • Track corrective actions from finding to close-out with full audit trail.

Book a demo to see how MapTrack handles portable appliances checklists.

Try MapTrack free for 30 days

Full access to every feature. No credit card required. Per-asset pricing so you scale as your fleet grows.

  • No credit card required
  • 30 days free trial
  • Cancel anytime

1-2 days/week saved

Bloody amazing! We used to spend 1-2 days a week tracking and managing our generators alone.
Saunders International

Steve McAllister

Asset Coordinator, Saunders International

What to include in a PAT testing checklist

This PAT testing checklist covers 10 key areas:

  • Register details: site or location, inspector or tester name, competency or qualification, test instrument make, model and calibration date.
  • Equipment details: unique asset ID or tag number, description (e.g. kettle, extension lead, power tool), make, model, Class I or Class II, location or department, owner or user.
  • Visual inspection: plug condition (pins, fuse rating, cord grip), cable condition (sheath, no cuts, joins or damage), equipment body (casing, ventilation, no overheating signs, no water ingress), labelling (correct voltage and frequency rating).
  • Earth continuity test (Class I only): test lead resistance compensation, measured resistance in ohms, pass or fail (typically less than 0.1 ohm for most equipment, up to 0.5 ohm for longer leads).
  • Insulation resistance test: test voltage (typically 500V DC for standard equipment, 250V DC for IT equipment), measured resistance in megohms, pass or fail (typically greater than 1 megohm).
  • Polarity test (where applicable): live and neutral correctly connected, pass or fail.
  • Functional test: equipment operates correctly when powered on, no abnormal heat, noise or smell.
  • Outcome: overall pass or fail, defect description if failed, action taken (repaired, withdrawn from service, scrapped).
  • Test label: unique ID, test date, next test due, tester initials, applied to the equipment.
  • Register entry: results recorded in the PAT testing register or asset management system for traceability.

How to use this PAT testing checklist

  1. Gather the test instrument (PAT tester), calibration certificate, checklist, test labels and the register of equipment to be tested. Verify the PAT tester is within its calibration date.: Check the calibration sticker or certificate on the PAT tester before commencing. If the calibration has expired, the tester must not be used. Prepare sufficient test labels, both pass and fail types, for the number of items to be tested.
  2. Unplug the appliance from the mains. Perform the visual inspection: check the plug (pins, fuse, cord grip), cable (sheath, no damage), equipment body (casing, ventilation, labelling) and record the results.: Inspect the plug pins for damage or discolouration, confirm the correct fuse rating is fitted and check the cord grip is secure. Examine the cable sheath for cuts, kinks or joins. Check the equipment body for cracks, overheating signs and clear ventilation.
  3. For Class I equipment, perform the earth continuity test. Connect the PAT tester and record the resistance. Pass is typically less than 0.1 ohm for short leads and up to 0.5 ohm for longer leads.: Connect the earth continuity lead to the earth pin of the plug and the other to an accessible metal part of the equipment. The tester applies a test current and measures the resistance of the earth path. Record the exact reading in ohms.
  4. Perform the insulation resistance test at 500V DC (or 250V DC for IT equipment). Record the measured resistance. Pass is typically greater than 1 megohm.: Select the correct test voltage on the PAT tester (500V DC for standard equipment, 250V DC for IT equipment and sensitive electronics to avoid damage). The tester measures insulation between live conductors and accessible metal parts. Record the reading in megohms.
  5. Perform a polarity check where applicable. Then conduct a functional test by powering on the appliance briefly and checking for normal operation, no abnormal heat, noise or smell.: The polarity check confirms live and neutral are correctly connected. For the functional test, plug the appliance in and switch it on briefly. Observe for normal operation, listen for unusual sounds and check for any abnormal heat or burning smell.
  6. Record the overall pass or fail outcome. If failed, describe the defect and action taken (repaired, withdrawn, scrapped). Apply a test label showing the unique ID, test date, next test due and tester initials.: For passed items, apply a pass label securely to the plug or cable. For failed items, apply a fail or danger label and remove the appliance from service immediately. Record the specific defect and the action taken in the register.
  7. Enter the results in the PAT testing register or asset management system. Set the next test due date based on the IET Code of Practice recommended intervals for the equipment type and environment.: Record all results against the unique asset ID in the register. Set the next test due date based on the equipment type and use environment as recommended by the IET Code of Practice. Review and adjust intervals based on failure rates over time.

In MapTrack, you can automate compliance tracking and audit trails. Each submission is stored as a timestamped PDF against the asset record.

Get the free templateEnter your email above to download the full PAT testing checklist as a PDF.Back to download form

How often should you complete this checklist?

PAT testing intervals are not fixed by law but are recommended by the IET Code of Practice based on a risk assessment considering the type of equipment, its use environment and the competence of users. Typical intervals are: IT equipment in an office (formal visual inspection every 2-4 years, combined inspection and test every 4-5 years), portable equipment on a construction site (user check daily, formal visual inspection weekly, combined inspection and test every 3 months), hand-held power tools in a workshop (user check before each use, formal visual inspection monthly, combined inspection and test every 6 months). New or refurbished equipment should be inspected and tested before first use. The IET Code of Practice emphasises that the initial suggested intervals should be reviewed and adjusted based on the results of previous inspections and the failure rate of equipment.

Frequently asked questions

PAT testing itself is not specifically mandated by any single piece of UK legislation. However, the Electricity at Work Regulations 1989 require that electrical equipment used in the workplace is maintained in a safe condition to prevent danger. The IET Code of Practice for In-Service Inspection and Testing of Electrical Equipment provides the accepted methodology for meeting this obligation. Employers, landlords and duty holders are expected to ensure portable electrical equipment is safe, and PAT testing is the industry-standard way to demonstrate compliance. The Health and Safety at Work etc. Act 1974 also places a general duty on employers to ensure the safety of equipment provided for use at work.

Class I equipment has basic insulation and relies on an earth connection for safety. If the insulation fails, fault current flows to earth through the earth conductor, tripping the protective device. Class I equipment requires an earth continuity test during PAT testing. Examples include kettles, toasters, metal-cased power tools and washing machines. Class II equipment (double insulated) has reinforced or double insulation and does not require an earth connection for safety. It is marked with a double-square symbol. Class II equipment does not need an earth continuity test but still requires visual inspection, insulation resistance testing and functional testing during PAT testing.

The IET Code of Practice recommends intervals based on equipment type and environment. Typical intervals are: office IT equipment, formal visual inspection every 2-4 years, combined inspection and test every 4-5 years. Construction site portable equipment, user check daily, formal visual inspection weekly, combined inspection and test every 3 months. Workshop hand-held power tools, user check before each use, formal visual inspection monthly, combined inspection and test every 6 months. These are starting points and should be adjusted based on failure rates and experience.

There is no legal requirement for a specific qualification to perform PAT testing. The IET Code of Practice states that the person carrying out the inspection and testing must be competent, meaning they have sufficient knowledge, training and experience to carry out the work safely and interpret the results correctly. In practice, many organisations use in-house staff who have completed a PAT testing training course (typically 1 day), or they engage an external PAT testing contractor. The person must understand the equipment being tested, the test procedures, the pass/fail criteria and the hazards involved.

For earth continuity testing on Class I equipment, the PAT tester applies a test current (typically 200 mA or 25 A, depending on the tester) and measures the resistance of the earth conductor. Pass is typically less than 0.1 ohm for most equipment. For insulation resistance testing, the standard test voltage is 500V DC for most equipment, or 250V DC for IT equipment and sensitive electronics to avoid damage. Pass is typically greater than 1 megohm. Always refer to the IET Code of Practice and your PAT tester manual for the correct settings for each equipment type.

Applicable regulatory standards

This template aligns with the following regulations and standards:

  • IET Code of Practice
  • Electricity at Work Regulations 1989

PAT Testing Checklist preview

PAT Testing Checklist template preview showing fields and layout

The numbers behind this PAT testing checklist

Every figure below is sourced and dated, so you can quote it in a toolbox talk, a budget case or a board paper without having to chase the original report.

Embed this free template on your website

Run an industry blog, trade association site, or training resource? Drop a preview of this free PAT testing checklist straight into your page. The snippet is self-contained, needs no scripts, and links readers back to the full free template.

<div style="max-width:480px;font-family:system-ui,-apple-system,'Segoe UI',Roboto,sans-serif;border:1px solid #E5E7EB;border-radius:12px;padding:20px;background:#ffffff;">
  <p style="font-size:12px;font-weight:700;letter-spacing:0.05em;text-transform:uppercase;color:#071D49;margin:0;">Free template</p>
  <p style="font-size:18px;font-weight:700;color:#071D49;margin:6px 0 0;">PAT Testing Checklist</p>
  <ul style="margin:12px 0 0;padding-left:18px;color:#374151;font-size:14px;line-height:1.6;">
    <li style="margin:4px 0;">Register details: site or location, inspector or tester name, competency or qualification, test instrument make, model and calibration date.</li>
    <li style="margin:4px 0;">Equipment details: unique asset ID or tag number, description (e.g. kettle, extension lead, power tool), make, model, Class I or Class II, location or department, owner or user.</li>
    <li style="margin:4px 0;">Visual inspection: plug condition (pins, fuse rating, cord grip), cable condition (sheath, no cuts, joins or damage), equipment body (casing, ventilation, no overheating signs, no water ingress), labelling (correct voltage and frequency rating).</li>
    <li style="margin:4px 0;">Earth continuity test (Class I only): test lead resistance compensation, measured resistance in ohms, pass or fail (typically less than 0.1 ohm for most equipment, up to 0.5 ohm for longer leads).</li>
    <li style="margin:4px 0;">Insulation resistance test: test voltage (typically 500V DC for standard equipment, 250V DC for IT equipment), measured resistance in megohms, pass or fail (typically greater than 1 megohm).</li>
    <li style="margin:4px 0;">Polarity test (where applicable): live and neutral correctly connected, pass or fail.</li>
  </ul>
  <p style="font-size:13px;color:#6B7280;margin:14px 0 0;padding-top:12px;border-top:1px solid #E5E7EB;">Free <a href="https://www.maptrack.com/templates/pat-testing-checklist" style="color:#071D49;font-weight:600;text-decoration:none;">PAT Testing Checklist</a> by MapTrack</p>
</div>

Free to reuse, including commercially. This template is published under a Creative Commons Attribution 4.0 licence. Copy it, adapt it, put it on your own site or in your own docs. All we ask is that you credit MapTrack with a link back to this page. The snippet above already includes that credit, so if you use it as-is you’re covered.

Cite this template

Writing about this topic? You’re welcome to quote this checklist. Here’s the wording to use so your readers can find the original.

The MapTrack PAT testing checklist contains 30 checks across 7 sections.

Short attribution
MapTrack PAT Testing Checklist, https://www.maptrack.com/templates/pat-testing-checklist
Reference list
MapTrack. (2026). PAT Testing Checklist [Checklist template]. Retrieved from https://www.maptrack.com/templates/pat-testing-checklist

Free to reuse with credit under a Creative Commons Attribution 4.0 licence. If you’d rather link straight to it, the page is https://www.maptrack.com/templates/pat-testing-checklist.

Need to automate compliance tracking and audit trails?

Register every portable appliances in MapTrack, attach digital forms, and get a complete history of every inspection, service and compliance record.

Compliance and inspections · All templates · Pricing · Book a demo