OSHA Electrical Safety Checklist

Workplace electrical inspection per 29 CFR 1910 Subpart S.

Your logo here
0 of 35 checks

Electrical Panels & Switchboards

1Panel covers secured, no missing or open knockouts
2Working clearance maintained (36 in. min per 1910.303(g))
3Circuit directory current, legible and matches installed circuits
4No storage of materials within panel working space
5Overcurrent devices (breakers/fuses) properly rated for circuit
6No signs of overheating, discoloration or burning at connections

Grounding & Bonding

7Equipment grounding conductor continuous and properly terminated
8Ground-fault protection devices functional (tested and verified)
9Bonding of metallic raceways and enclosures intact
10Grounding electrode connection secure and free of corrosion
11GFCIs tested (test/reset) and tripping within parameters

Wiring & Cords

12Flexible cords not used as substitute for permanent wiring
13Cord condition: no splices, fraying or exposed conductors
14Strain relief intact at all cord connections and plugs
15Correct cord type used for the environment (wet, outdoor, temp)
16Extension cords not daisy-chained or connected in series
17Cords not routed through walls, ceilings, floors or doorways

Receptacles & Switches

18Cover plates in place on all receptacles and switches
19Grounding-type receptacles installed where required
20No reverse polarity detected (verified with tester)
21Wet-location covers (in-use type) present and functional
22Switches and receptacles in good condition, securely mounted

Guarding of Live Parts

23Live parts at 50V+ guarded per 1910.303(g)(2) (enclosures, barriers, elevation)
24Warning signs posted on high-voltage enclosures and rooms
25Barriers and guards intact, not bypassed or removed
26Adequate illumination provided in electrical rooms and vaults

Electrical Equipment Condition

27Motors and machinery properly grounded per manufacturer specs
28No exposed wiring or damaged insulation on fixed equipment
29Disconnect switches accessible, labeled and operable
30Portable electrical equipment inspected before use (visual check)
31Listed/labeled equipment used per manufacturer instructions only

Emergency & Safety

32Fire extinguisher (Class C rated) accessible within 50 ft of panels
33First aid kit and AED available and location clearly marked
34Emergency disconnects identified, labeled and accessible
35Electrical safety PPE available (insulated gloves, face shield, arc-rated clothing)

Inspector Sign-off

Signature

Print name

Date & time

Supervisor / Facility Manager Acknowledgment

Signature

Print name

Date

How to use: download the PDF, print or complete digitally on any device.

  • PDF format, ready to print or fill on screen
  • Use as-is or customise to suit your operation
  • Go digital in MapTrack for photos, alerts and audit trails

Two ways to use it

Use in MapTrack →

Download the free PDF

Use it digitally instead

Unlimited users

These same 35 checks, already built.

G2 rating 4.9 out of 5Capterra rating 5.0 out of 5
  • Scan the asset’s QR tag with any phone
  • Submitted forms can trigger alerts
  • Photos on fails, audit-ready records
  • Export responses, PDF reports with your logo

Free trial. No credit card needed.

Trusted by teams across Australia and New Zealand

We respect your privacy. Unsubscribe anytime.

These templates are free general guides provided as-is. They do not constitute legal, safety or compliance advice. You are responsible for ensuring any form meets your specific workplace obligations, industry standards and applicable regulations.

Don't just download it - use it live. Start a free workspace with this OSHA electrical safety checklist already built, so your crew can run it from a phone.

Jarrod Milford

Jarrod Milford

Commercial Director

Updated 10 August 2026

Key takeaways

  • The MapTrack OSHA electrical safety checklist contains 35 checks across 7 sections. Sections covered: Electrical Panels & Switchboards, Grounding & Bonding, Wiring & Cords, Receptacles & Switches, Guarding of Live Parts, Electrical Equipment Condition, Emergency & Safety.

Enter your email below to download this OSHA electrical safety checklist as a ready-to-use PDF.

Used by construction, mining and field service teams

Saunders InternationalMineral ResourcesSupagasHacer GroupMetro TunnelUltrabuilt

What is a OSHA electrical safety checklist?

An OSHA electrical safety checklist is a structured inspection document used to verify that electrical installations, equipment and work practices comply with OSHA 29 CFR 1910 Subpart S (Electrical) requirements. It covers panel boards, circuit breakers, grounding and bonding, ground fault circuit interrupters (GFCIs), working clearances, flexible cords, receptacles, junction boxes, labeling and arc flash hazard identification. Each item is marked Pass, Fail or N/A with space for defect notes and corrective actions.

Electrical hazards are among the top causes of workplace fatalities and serious injuries in the United States. OSHA 29 CFR 1910.303 through 1910.335 establish the minimum requirements for electrical safety in general industry workplaces. Regular documented inspections using a standardized checklist help employers identify hazards such as missing covers, improper grounding, damaged cords, blocked working clearances and missing arc flash labels before they result in electrocution, burns or arc flash incidents. This checklist provides a repeatable, auditable framework that safety teams and qualified electricians can use for routine workplace electrical inspections.

Learn more about compliance and inspections in MapTrack.

Benefits of using this OSHA electrical safety checklist

  • OSHA compliance: documented inspections demonstrate compliance with 29 CFR 1910 Subpart S and reduce the risk of citations during OSHA inspections.
  • Electrocution prevention: identifying missing grounds, damaged insulation and improper bonding before they cause contact with energized parts.
  • Arc flash risk reduction: verifying arc flash labels, working clearances and PPE requirements reduces the severity of arc flash incidents.
  • Fire prevention: catching overloaded circuits, damaged cords, missing covers and improper connections prevents electrical fires.
  • Insurance support: a documented electrical safety inspection program supports insurance underwriting and can reduce premiums.
  • Consistent standards: a standardized checklist ensures every facility and panel board is inspected to the same criteria regardless of which inspector performs the work.

Benefits of digitising forms in MapTrack

When you digitise electrical equipment checklists in MapTrack, you get:

  • Field users can easily scan a QR code to complete a form on mobile. Unlimited users.
  • Automatically get alerts when faults are identified.
  • Link every form digitally as a PDF to the relevant asset, location or person.
  • Receive a digital PDF copy with every submission to your email.
  • Ability to share forms digitally.
  • Build conditional logic (show or hide questions based on answers).
  • Take pictures or attach photos. Not possible with a paper-based form.
  • Electronic signatures.
  • Edit forms later without reprinting.
  • Restrict permissions (who can view, complete or approve).
  • Build forms with AI (describe what you need and MapTrack suggests the form).
  • Auto-apply the correct regulatory standard (OSHA, HSE, WHS) based on site location.
  • Generate region-specific compliance reports that match local regulator expectations.
  • Track jurisdiction-specific inspection intervals and certification requirements.

Book a demo to see how MapTrack handles electrical equipment checklists.

Try MapTrack free for 30 days

Full access to every feature. No credit card required. Per-asset pricing so you scale as your fleet grows.

  • No credit card required
  • 30 days free trial
  • Cancel anytime

1-2 days/week saved

Bloody amazing! We used to spend 1-2 days a week tracking and managing our generators alone.
Saunders International

Steve McAllister

Asset Coordinator, Saunders International

What to include in a OSHA electrical safety checklist

This OSHA electrical safety checklist covers 10 key areas:

  • Facility and inspector details: facility name, building, area, inspector name, qualification, date and inspection type (routine, annual, post-incident).
  • Panel boards and switchboards: cover plates in place, directory current and legible, breakers labeled, no evidence of overheating, working clearance maintained per 1910.303(g).
  • Grounding and bonding: equipment grounding conductors intact, bonding jumpers present, ground rods accessible, grounding electrode system intact.
  • GFCIs: all required GFCI receptacles installed, monthly test/reset function verified, GFCI protection on outdoor, wet and temporary power circuits.
  • Working clearances: minimum clearances per 1910.303(g) maintained in front of all panels (36 inches minimum for 0-150V), no storage in electrical rooms.
  • Flexible cords and receptacles: cords not used as permanent wiring, no damage or splices, strain relief present, receptacles not loose or broken, covers on unused outlets.
  • Junction boxes and conduit: all covers in place, no open knockouts, conduit secure and continuous, no exposed wiring.
  • Arc flash labeling: arc flash hazard labels present on all panels per NFPA 70E, incident energy or PPE category displayed, approach boundaries marked where required.
  • Extension cords and temporary wiring: used only as permitted by 1910.305(a), three-wire type, grounded, not daisy-chained, not run through doors, windows or ceilings.
  • Overall result: Pass/Fail with defect register, corrective action assignments and follow-up dates.

How to use this OSHA electrical safety checklist

  1. Record the facility, building, area, inspector name, qualification, date and inspection type at the top of the form.: Only qualified persons as defined by OSHA should perform electrical safety inspections. Record your electrical qualification (licensed electrician, NFPA 70E qualified worker, safety professional) and the scope of the inspection. Note whether this is a routine monthly, annual comprehensive or post-incident inspection.
  2. Inspect each electrical panel board: verify covers are in place, directory is current, breakers are labeled, working clearance is maintained and there are no signs of overheating.: Open each panel board cover and visually inspect for signs of overheating (discolored wires, melted insulation, burn marks). Verify the panel directory matches the actual circuit configuration. Confirm minimum working clearance of 36 inches (for 0-150V) or 42 inches (151-600V) is maintained per 1910.303(g)(1). Note any breakers in the tripped position.
  3. Check grounding and bonding: verify equipment grounding conductors, bonding jumpers, ground rods and the grounding electrode system are intact and accessible.: Confirm that all equipment grounding conductors are continuous and connected. Check bonding jumpers at water pipes, structural steel and other metallic systems. Verify ground rod connections are accessible and not buried. If the facility has a ground resistance testing schedule, confirm the last test result is within acceptable limits.
  4. Test all GFCI receptacles, inspect flexible cords and receptacles, check junction boxes and conduit for completeness.: Press the test button on each GFCI receptacle to verify it trips, then reset. Check that GFCIs are installed on all required circuits including outdoor, wet location, bathroom and temporary power. Inspect every visible flexible cord for damage, splices, strain relief and proper grounding. Confirm all junction box covers are in place with no open knockouts.
  5. Verify arc flash labels are present on all panels, check extension cord usage and inspect temporary wiring installations.: Confirm that every panel board, switchboard and motor control center has an arc flash hazard label per NFPA 70E with either the incident energy level or the PPE category. Check that extension cords are three-wire grounded type, not daisy-chained and not used as permanent wiring. Verify any temporary wiring complies with 1910.305(a) requirements.
  6. Record all defects, select the overall result (Pass or Fail), assign corrective actions with due dates and sign the form.: Document every failed item with a description, the specific OSHA standard reference (e.g., 1910.303(g)(1) for working clearance), severity and corrective action. Immediately de-energize and lock out any condition that presents an imminent danger of electrocution or arc flash. Sign the form and submit it to the facility safety manager for review and corrective action tracking.

In MapTrack, you can digitise regulatory compliance forms for your region. Each submission is stored as a timestamped PDF against the asset record.

Get the free templateEnter your email above to download the full OSHA electrical safety checklist as a PDF.Back to download form

How often should you complete this checklist?

OSHA does not prescribe a specific inspection frequency for general electrical safety, but 29 CFR 1910.303 requires that electrical equipment be maintained in a safe condition. Industry best practice is to conduct a comprehensive electrical safety inspection at least annually, with monthly visual checks of panel boards, GFCIs and cord-connected equipment. Facilities with higher electrical risk (manufacturing, data centers, laboratories) should consider quarterly comprehensive inspections.

GFCI receptacles should be tested monthly per manufacturer instructions. Arc flash studies should be updated every five years or whenever a major electrical modification is made, per NFPA 70E. After any electrical incident, near miss or modification to the electrical system, a targeted inspection should be performed before the affected equipment is returned to service.

Frequently asked questions

OSHA 29 CFR 1910 Subpart S requires employers to ensure that electrical equipment is installed and maintained in a safe condition. While OSHA does not mandate a specific inspection frequency, the general duty clause and specific standards like 1910.303 (general requirements), 1910.305 (wiring methods) and 1910.335 (safeguards for personnel protection) establish the criteria that must be met. Regular documented inspections are the most effective way to demonstrate ongoing compliance and identify hazards before they cause injuries.

Industry best practice recommends a comprehensive electrical safety inspection at least annually, with monthly visual checks of panel boards, GFCIs and cord-connected equipment. Higher-risk facilities may require quarterly inspections. GFCI receptacles should be tested monthly. Arc flash studies should be updated every five years or after major electrical modifications per NFPA 70E. After any electrical incident, near miss or system modification, a targeted inspection should be performed immediately.

OSHA 29 CFR 1910.303(g)(1) requires minimum working clearances in front of electrical equipment. For 0-150V nominal: 36 inches. For 151-600V nominal with grounded parts on the opposite side: 36 inches; with ungrounded parts on the opposite side: 42 inches. For over 600V, clearances increase further. These clearances must be maintained at all times, meaning no storage, equipment or materials may be placed within the clearance zone.

An OSHA electrical inspection verifies compliance with 29 CFR 1910 Subpart S, which covers the installation and maintenance of electrical systems and equipment. An NFPA 70E assessment focuses on electrical safety practices for workers, including arc flash hazard analysis, shock risk assessment, PPE selection and safe work practices. In practice, a comprehensive workplace electrical safety program includes both: the physical installation inspection (OSHA) and the worker protection assessment (NFPA 70E).

Yes. Download and use this OSHA electrical safety checklist at no cost. Open the file in your browser and use Print then Save as PDF for a paper copy. No MapTrack account is required. If you want digital electrical safety inspections on mobile with photo capture, automatic defect escalation to work orders, panel-level compliance tracking and scheduled inspection reminders, MapTrack can do that. Book a demo to see how it works.

Applicable regulatory standards

This template aligns with the following regulations and standards:

  • OSHA 29 CFR 1910.303 (General requirements for electrical installations)
  • OSHA 29 CFR 1910.305 (Wiring methods, components and equipment)
  • NFPA 70E (Standard for Electrical Safety in the Workplace)

OSHA Electrical Safety Checklist preview

OSHA Electrical Safety Checklist template preview showing fields and layout

The numbers behind this OSHA electrical safety checklist

Every figure below is sourced and dated, so you can quote it in a toolbox talk, a budget case or a board paper without having to chase the original report.

Embed this free template on your website

Run an industry blog, trade association site, or training resource? Drop a preview of this free OSHA electrical safety checklist straight into your page. The snippet is self-contained, needs no scripts, and links readers back to the full free template.

<div style="max-width:480px;font-family:system-ui,-apple-system,'Segoe UI',Roboto,sans-serif;border:1px solid #E5E7EB;border-radius:12px;padding:20px;background:#ffffff;">
  <p style="font-size:12px;font-weight:700;letter-spacing:0.05em;text-transform:uppercase;color:#071D49;margin:0;">Free template</p>
  <p style="font-size:18px;font-weight:700;color:#071D49;margin:6px 0 0;">OSHA Electrical Safety Checklist</p>
  <ul style="margin:12px 0 0;padding-left:18px;color:#374151;font-size:14px;line-height:1.6;">
    <li style="margin:4px 0;">Facility and inspector details: facility name, building, area, inspector name, qualification, date and inspection type (routine, annual, post-incident).</li>
    <li style="margin:4px 0;">Panel boards and switchboards: cover plates in place, directory current and legible, breakers labeled, no evidence of overheating, working clearance maintained per 1910.303(g).</li>
    <li style="margin:4px 0;">Grounding and bonding: equipment grounding conductors intact, bonding jumpers present, ground rods accessible, grounding electrode system intact.</li>
    <li style="margin:4px 0;">GFCIs: all required GFCI receptacles installed, monthly test/reset function verified, GFCI protection on outdoor, wet and temporary power circuits.</li>
    <li style="margin:4px 0;">Working clearances: minimum clearances per 1910.303(g) maintained in front of all panels (36 inches minimum for 0-150V), no storage in electrical rooms.</li>
    <li style="margin:4px 0;">Flexible cords and receptacles: cords not used as permanent wiring, no damage or splices, strain relief present, receptacles not loose or broken, covers on unused outlets.</li>
  </ul>
  <p style="font-size:13px;color:#6B7280;margin:14px 0 0;padding-top:12px;border-top:1px solid #E5E7EB;">Free <a href="https://www.maptrack.com/templates/osha-electrical-safety-checklist" style="color:#071D49;font-weight:600;text-decoration:none;">OSHA Electrical Safety Checklist</a> by MapTrack</p>
</div>

Free to reuse, including commercially. This template is published under a Creative Commons Attribution 4.0 licence. Copy it, adapt it, put it on your own site or in your own docs. All we ask is that you credit MapTrack with a link back to this page. The snippet above already includes that credit, so if you use it as-is you’re covered.

Cite this template

Writing about this topic? You’re welcome to quote this checklist. Here’s the wording to use so your readers can find the original.

The MapTrack OSHA electrical safety checklist contains 35 checks across 7 sections.

Short attribution
MapTrack OSHA Electrical Safety Checklist, https://www.maptrack.com/templates/osha-electrical-safety-checklist
Reference list
MapTrack. (2026). OSHA Electrical Safety Checklist [Checklist template]. Retrieved from https://www.maptrack.com/templates/osha-electrical-safety-checklist

Free to reuse with credit under a Creative Commons Attribution 4.0 licence. If you’d rather link straight to it, the page is https://www.maptrack.com/templates/osha-electrical-safety-checklist.

Need to digitise regulatory compliance forms for your region?

Register every electrical equipment in MapTrack, attach digital forms, and get a complete history of every inspection, service and compliance record.

Compliance and inspections · All templates · Pricing · Book a demo